New Delivery for Preformed Armour Rod - composite polymer tension insulator – Waxun
New Delivery for Preformed Armour Rod - composite polymer tension insulator – Waxun Detail:
FXBW-T-WQ Rod type composite bird proof insulator
Introduction
This product includes insulating Core, insulating housing & weather sheds and terminal assembly parts.
1. The Insulating Core: The insulating core is made of epoxy resin impregnated glass fiber by winding or extruding. Tensile strength is generally up to 1100Mpa or more, 3 times of the ordinary steel and 5 to 8 times of porcelain material.
2. The Housing and Weather Sheds: With the automatic silicone rubber injection molding machine, the housing & weather sheds adopts the one-time integral molding process under high temperature and high pressure, which ensures the binding force between the silicone rubber and core and the sealing property of the end attachment. The most critical problem of the insulator, interface electrical breakdown, is solved.
3. The Ending Fitting: End fitting is made of special steel. With labyrinth design at the terminal, the sealing performance is excellent under multi-layer protection.
FXBW-T-WQ Rod type composite bird proof insulator | ||||||||
Type | Rated voltage(KV) | Rated Machinery load(KN) | Structural height(mm) | Insulation distance(mm) | Minimum nominal creepage distance (mm) | lightning impulse withstand voltage (peak kv) | 1min Power-frequency withstand voltage (RMS) | The first big umbrella diameter(mm) |
FXBW4-35/70T-WQ | 35 | 70 | 660 | 460 | 1260 | 230 | 95 | 250/300 |
FXBW4-35/100T-WQ | 35 | 100 | 700 | 460 | 1260 | 230 | 95 | 250/300 |
FXBW4-66/70T-WQ | 66 | 70 | 900 | 720 | 2250 | 410 | 185 | 250/300 |
FXBW4-66/100T-WQ | 66 | 100 | 940 | 720 | 2250 | 410 | 185 | 250/300 |
FXBW4-110/70T-WQ | 110 | 70 | 1200 | 1000 | 3150 | 550 | 230 | 250/300 |
FXBW4-110/100T-WQ | 110 | 100 | 1240 | 1000 | 3150 | 550 | 230 | 250/300 |
FXBW4-110/100T-WQ1 | 110 | 100 | 1280 | 1040 | 3200 | 560 | 240 | 250/300 |
FXBW4-110/100T-WQ3 | 110 | 100 | 1360 | 1120 | 3400 | 580 | 250 | 250/300 |
FXBW4-110/100T-WQ5 | 110 | 100 | 1440 | 1200 | 3600 | 600 | 260 | 250/300 |
FXBW4-110/120T-WQ | 110 | 120 | 1240 | 1000 | 3150 | 550 | 230 | 250/300 |
FXBW4-220/70T-WQ | 220 | 70 | 2170 | 1960 | 6300 | 1000 | 395 | 250/300 |
FXBW4-220/100T-WQ | 220 | 100 | 2210 | 1960 | 6300 | 1000 | 395 | 250/300 |
High voltage pin type composite insulator and line post type composite insulator
Overview
Apply to power plant facilities, has the good hydrophobic, aging resistance, resistance to tracking and electrical erosion resistance, high tensile strength, bending strength, its high mechanical strength, good shock resistance, shock and can prevent brittleness, light weight, easy installation, the installation at the top and bottom size the same as the corresponding porcelain pillar installation size, can be used interchangeably.
High voltage pin type composite insulator and line post type composite insulator |
||||||||
Type |
Rated voltage(KV) |
Rated Machinery load(KN) |
Structural height(mm) |
Insulation distance(mm) |
Minimum nominal creepage distance (mm) |
lightning impulse withstand voltage (peak kv) |
Power-frequency withstand voltage (effective value KV) |
Creepage distance |
FQP1-6/4T12 |
6 |
4 |
210 |
113 |
205 |
60 |
28 |
27 |
FQP2-10/4T20 |
10 |
4 |
207 |
140 |
380 |
90 |
40 |
26 |
FQP3-10/4T20 |
10 |
4 |
247 |
170 |
460 |
105 |
45 |
36 |
FQP-20/4T20 |
20 |
4 |
345 |
265 |
740 |
125 |
65 |
30 |
FQP-35/5T20 |
35 |
5 |
640 |
500 |
1020 |
230 |
95 |
25 |
FPS-105/5T20 |
10 |
5 |
247 |
200 |
460 |
105 |
45 |
36 |
FZS Rod post composite insulator
Overview
Apply to power plant facilities, has the good hydrophobic, aging resistance, resistance to tracking and electrical erosion resistance, high tensile strength, bending strength, its high mechanical strength, good shock resistance, shock and can prevent brittleness, light weight, easy installation, the installation at the top and bottom size the same as the corresponding porcelain pillar installation size, can be used interchangeably.
FZS Rod post composite insulator | |||||||||
Type | Rated voltage(KV) | Rated Machinery load(KN) | Structural height(mm) | Insulation distance(mm) | Minimum nominal creepage distance (mm) | lightning impulse withstand voltage (peak kv) | Power-frequency withstand voltage (effective value KV) | Creepage distance | Distance from center of mounting hole(mm) |
FZS-10/4 | 12 | 4 | 230 | 140 | 300 | 75 | 45 | 25 | 76 |
FZSW-20/6 | 24 | 6 | 330 | 230 | 650 | 125 | 65 | 25 | 76/140 |
FZSW-35/6 | 40.5 | 6 | 450 | 350 | 1020 | 230 | 95 | 25 | 76 |
FZSW-35/6 | 40.5 | 6 | 450 | 350 | 1020 | 230 | 95 | 25 | 140 |
FZSW-66/8 | 72.5 | 8 | 770 | 630 | 2100 | 410 | 185 | 25 | 140 |
FZSW-110/10 | 126 | 10 | 1230 | 1060 | 3150 | 550 | 230 | 25 | 140/225 |
FZSW-220/5 | 252 | 5 | 2460 | 2100 | 6300 | 1000 | 395 | 25 | 140/225 |
Rod composite export type insulator
Composite tension-resistant insulators are suitable for use in polluted areas, especially in heavy polluted areas, with high tensile strength, good anti-pollution performance and easy installation and use.
Rod composite export type insulator | ||||||||
Type | Rated voltage(KV) | Rated Machinery load(KN) | Structural height(mm) | Insulation distance(mm) | Minimum nominal creepage distance (mm) | The first big umbrella diameter(mm) | lightning impulse withstand voltage (peak kv) | 1min Power-frequency withstand voltage (RMS) |
FXBW4-12/70 | 12 | 70 | 390 | 200 | 450 | 123/98 | 42 | 95 |
FXBW4-15/70 | 15 | 70 | 445 | 225 | 620 | 98 | 50 | 105 |
FXBW4-22/70 | 22 | 70 | 480 | 270 | 744 | 130/94 | 65 | 125 |
FXBW4-24/70 | 24 | 70 | 480 | 280 | 635 | 98 | 68 | 130 |
FXBW4-28/70 | 28 | 70 | 660 | 450 | 1200 | 144/116 | 95 | 230 |
FXBW4-33/70 | 33 | 70 | 660 | 450 | 1200 | 144/116 | 95 | 230 |
FXBW4-35/70 | 35 | 70 | 660 | 450 | 1200 | 144/116 | 95 | 230 |
FXBW4-36/70 | 36 | 70 | 660 | 450 | 1200 | 144/116 | 95 | 230 |
FXBW4-WQ Rod composite tension insulator
Overview
Composite tension-resistant insulators are suitable for use in polluted areas, especially in heavy polluted areas, with high tensile strength, good anti-pollution performance and easy installation and use.
Feature
1. Shed connected with core by integral foring
2. The thinkness of housing > 3mm, unifirm to IEC Standard
3. Acid resistant,high temperature resistant of epoxy fiberglass core
4. Metal end fittings,core and sheds connected by new crimping process
5. Hot galvanization and technology of rare earth aluminum coating to avoid coating
shedding prolonging the service life
1)Small volume,light weight,sheds have good elasticity,not broken,convenient
transportation and installation.
(2)High mechanical strength FRP ROD has high tensile strength, small size,light
weight,high tensile strength.
(3)High antifouling property,good aging resistance performance,high anti pollution
flashover voltage , good electric corrosion resistance.
(4)Easy installation,greatly reduce maintaince charges and manual labor intensity.
(5)Simple production process,short delivery time.
FXBW4-WQ Rod composite tension insulator | |||||||
Type | Rated voltage(KV) | Rated Machinery load(KN) | Structural height(mm) | Insulation distance(mm) | Minimum nominal creepage distance (mm) | lightning impulse withstand voltage (peak kv) | 1min Power-frequency withstand voltage (RMS) |
FXBW4-10/70-WQ | 10 | 70 | 380 | 200 | 480 | 95 | 45 |
FXBW4-10/100-WQ | 10 | 100 | 420 | 200 | 480 | 95 | 45 |
FXBW4-20/70-WQ | 22 | 70 | 460 | 280 | 744 | 125 | 65 |
FXBW4-20/100-WQ | 22 | 100 | 500 | 280 | 744 | 125 | 65 |
FXBW4-35/70-WQ | 35 | 70 | 640 | 450 | 1200 | 230 | 95 |
FXBW4-35/100-WQ | 35 | 100 | 680 | 450 | 1200 | 230 | 95 |
FXBW4-66/70-WQ | 66 | 70 | 900 | 720 | 2250 | 410 | 185 |
FXBW4-66/100-WQ | 66 | 100 | 940 | 720 | 2250 | 410 | 185 |
FXBW4-110/70-WQ | 110 | 70 | 1200 | 1000 | 3150 | 550 | 230 |
FXBW4-110/100-WQ | 110 | 100 | 1240 | 1000 | 3150 | 550 | 230 |
FXBW4-110/100-WQ1 | 110 | 100 | 1280 | 1040 | 3200 | 560 | 240 |
FXBW4-110/100-WQ3 | 110 | 100 | 1360 | 1120 | 3400 | 580 | 250 |
FXBW4-110/100-WQ5 | 110 | 100 | 1440 | 1200 | 3600 | 600 | 260 |
FXBW4-100/120-WQ | 110 | 120 | 1240 | 1000 | 3150 | 550 | 230 |
FXBW4-220/100-WQ | 220 | 100 | 2210 | 1960 | 6300 | 1000 | 395 |
FXBW4-220/160-WQ | 220 | 160 | 2240 | 1960 | 5900 | 1000 | 395 |
FXBW4-330/160-WQ | 330 | 160 | 2990 | 2700 | 8300 | 425 | 570 |
FXBW4-500/160-WQ | 500 | 160 | 4450 | 4150 | 12900 | 2250 | 740 |
FXBW4-XX Rod composite tension insulator
Composite tension-resistant insulators are suitable for use in polluted areas, especially in heavy polluted areas, with high tensile strength, good anti-pollution performance and easy installation and use.
Polymer Insulator Character
1.1 High mechanical strength;
1.2 Good performance of hydrophobicity and anti-pollution;
1.3 Excellent electrical Performance;
1.4 Small volume and light weight.
TID polymer Insulator Character
2.1 We adopt the advanced injection producing technology for housing and the design of the shed adopt unique aerodynamics principle.
2.2 Good Raw material :
We use HTV silicone rubber which hydrophobicity can reach to HC1 level
We use hot dip Galvanizing steel fitting ,the thickness of the zinc more than 100 μm.
We use ECR rod as the core which is high acid resistant. 7200Hr testing passed .
2.3 Special marking design.
We use the double seal design between the rubber and the fitting.
We can mark your logo on the fitting or rubber.
2.4 Excellent Manufacture Technology:
Perfect match between fitting and rod
Perfect bound between silicone rubber and the rod
FXBW4-XX Rod composite tension insulator | |||||||
Type | Rated voltage(KV) | Rated Machinery load(KN) | Structural height(mm) | Insulation distance(mm) | Minimum nominal creepage distance (mm) | lightning impulse withstand voltage (peak kv) | 1min Power-frequency withstand voltage (RMS) |
FXBW4-1/70XX | 1 | 70 | 300 | 110 | 280 | 30 | 7 |
FXBW4-6/70XX | 6 | 70 | 340 | 150 | 360 | 60 | 25 |
FXBW4-10/70XX | 10 | 70 | 380 | 200 | 480 | 95 | 45 |
FXBW4-15/70XX | 15 | 70 | 420 | 240 | 600 | 110 | 60 |
FXBW4-20/70XX | 20 | 70 | 460 | 290 | 720 | 130 | 70 |
FXBW4-24/70XX | 24 | 70 | 460 | 290 | 720 | 150 | 75 |
FXBW4-28/70XX | 28 | 70 | 640 | 335 | 840 | 180 | 85 |
FXBW4-33/70XX | 33 | 70 | 680 | 380 | 960 | 205 | 90 |
FXBW4-35/70XX | 35 | 70 | 680 | 380 | 960 | 230 | 95 |
FXBW4-35/70XX | 35 | 70 | 680 | 380 | 960 | 230 | 95 |
Product detail pictures:
Related Product Guide:
We support our purchasers with ideal high-quality merchandise and significant level company. Becoming the specialist manufacturer in this sector, we now have received loaded practical encounter in producing and managing for New Delivery for Preformed Armour Rod - composite polymer tension insulator – Waxun, The product will supply to all over the world, such as: Indonesia, Czech Republic, Hanover, We also have the strong ability of integration to supply our best service, and plan to build the warehouse in the different countries around the world, that will probably be more conveniently to service our customers.