Loadbreak Elbow Connector

Short Description:

Loadbreak Elbow Connector is fully insulated, fully sealed connector, is widely used in outdoor power distribution transformer, American cabinet type

transformer, ring main unit and cable branch box, buried transformers and other electrical equipments. It can be installed on outgoing line of 200AT type connector, 200A busbar, single-pass(Double type) apparatus bushing and load conversion connector of American cabinet type transformer.

Test points can be installed live monitor, in order to check the charged state of the equipment, but also to meet the nuclear phase requirements.

Conductive rod connector arc extinguishing material, it can be charged in the state operation, but can not cut off the short-circuit current; can be used as the load switch to open the current 200A.

Applicable for XLPE cable cross-section 25mm2-400mm2

 

 

 

 

 


Product Detail

Product Tags

Description

15kV 200A Loadbreak Elbow Connector is a fully-shielded and insulated plug-in termination  for connecting underground cable to distribution power system of pad-mound transformer ,  surrounding power supply branch box , cable branch box equipped with loadbreak bushings . The  elbow connector and bushing insert comprise the essential components of all loadbreak  connections. It can meet the demand of lines in nuclear. The Loadbreak Elbows are molded using high quality sulfur-cured insulating and semi-  conducting EPDM rubber.Standard features include a coppertop connector, tin-plated copper  loadbreak probe with an ablative arc-follower tip and stainless steel reinforced pulling-eye . An  optional capacitive test point , made of corrosion resistant plastic , is available for use with fault  indicators. The avaible conductor cross section is 35~150mm2 for 15kV cable. The conductive pole W/ARC  extinguishes function.

Product Structure

1. Operating ring: one-piece molded stainless steel operating ring with spring clip fixing poin.

2.Insulating layer: Special formula and mixing technology to ensure high quality of prefabricated rubber

3.Internal semi conductive layer: prefabricated inner semi conductive layer to effectively control the stress of electric field

4.Outer semi conductive layer: The prefabricated outer semi conductive layer adheres closely to the insulating layer and ensures that the outer semi

conductive layer is grounded.

5.Arcing rod: Tin plated copper rod with arc extinguishing function,use a wrench to screw it into the conductive connection in the device.

6.Terminals: All copper or cooper and aluminum crimp terminals for copper or aluminum conductor.

7.Voltage test: It is used to test whether the line is electrified or not and the live indicator is used.

Standard packing

Plug pole、Silicone grease、Instruction Manual、Spanner、Towels、Body of connector, cap of test point、earth wire、

crimp terminals、conformity certificate

 