Insulated piercing connector (fire prevention)

Short Description:

Material

Body: Thermoplastic polyamide 66 with fiberglass
Connecting bridge: Copper tinned, Brass tinned, Al
Sealing parts: Flexible PVC
End cap: Flexible PVC
Grease: Silica gel
Bolt: Hot dip glavanized steel, 8.8 grade
Washer, Nut: Hot dip glavanized steel
Fuse nut: Zinc alloy


Product Detail

Product Tags

1KV Insulated piercing connector
Type Run (mm²) Tap(mm²) Current(A) Size(mm) Weight(g) Piercing depth(mm) Bolt Qty.(pcs)
JJC-1 1.5-25 1.5-10 55 27*41*62 55 1.5-2 1
JJC-2 16-95 1.5-10 55 27*41*62 55 1-2 1
JJC-3-1 6-50 4-25 157 42*45*62 110 2.5-3.5 1
JJC-3 16-95 4-35(50) 157 46*52*87 160 2.5-3.5 1
JJC-4 50-150 6-35(50) 157 46*52*87 162 2.5-3.5 1
JJC-5 25-95 25-95 214 50*61*100 198 3-4 1
JJC-5-1 16-120 16-120 214 50*61*100 198 3-4 1
JJC-6 (35)50-150 (35)50-150 316 50*61*100 280 3-4 1
JJC-7 120-240 25-120 276 52*68*100 360 3-4 1
JJC-7-1 150-240 10-25 102 52*68*100 336 3-4 1
JJC-8 95-240 95-240 425 83*130*130 1020 4-5 2

The Low voltage waterproof copper tinned teeth Insulation cable clamp / Insulated piercing Connector is suitable for majority types of LV ABC conductors as well as connections to service and lighting cable cores. When tightening the bolts, the teeth of the contact plates penetrate the insulation and establish a perfect contact. The bolts are tightened until the heads shear off. Tightening torque guaranteed(fuse nut). Stripping of insulation is avoided.
Service condition: 400/600V, 50/60Hz, -10°C to 55°C