Euromold Screened Separable Connectors
Application
·For connection ofpolymeric cable to transformers, switchgear, motors and otherequip ment with a premoulded separable connector.
·For indoor and outdoor installations.
·System voltage up t0 24 kV.
·Continuous cu rrent 630A(900 A ove rload for 8 hou rs).
·Cable particulars:
-Polymeric cable (XLPE, EPR, etc.)
-Copper or aluminum conductors
-Semiconducting or metallic screens
-Conductor size 12kV 25-120mm2 24kV 25-400mm²
Features
Provides a fully screened and fully submersible separable connection when mated with the proper bushing or plug;
Can be used under the circumstances,
Built-in capacitive test point to determine the circuit status or installa fault indicator
·No minimum phase clearance requirements;
Mounting can be vertical, horizontal, or any angle in between.
12KV
24KV
Installation
Without any special tools
·When finish the installation of elbow connector, the power can be supply directly.
·T Fore connector
·Insulator
·Covering cap
·Adaptor
·Conductor cable lug
·Two-head Screw
·Silicone Lubricant, Clearing Paper
·Installation Instruction Sheet
·Quality Certificate